ISOLATION TRANSFORMERS

simbolo2

Single-Phase Isolation Transformer

220 / 227 / 380 / 480VAC -

110 / 220VAC

Details

PRIMARY VOLTAGE: 220 / 227 / 380 / 480VAC
SECONDARY VOLTAGE: 110 / 220VAC
STANDARD: In accordance with EN-61558-2-4
ISOLATION CLASS: T40/F
DIELECTRIC STRENGTH:
4800V (between primary and secondary)
3500V (between primary and mass)

PROTECTION DEGREE: IP00
PROTECTION CLASS: I
FREQUENCIES: 50 / 60Hz
CONNECTION: Screw faston terminals
FIXINGS: Using angles DIN 41307
WINDING: Enamelled copper wire class H. Separated primary and secondary (galvanic separation)

Isolation transformers are intended to supply electric devices where a circuit separation is required. Protected against humidity by means of resin impregnation

Code: 

SPECIFICATIONS

TECHNICAL FEATURES

Power (KVA)CodeDimension ADimension BDimension CDimension DDimension HDimension MxNWeight (Kg)Packing
40TF09040410084999064519x4,81.412
63TF090634100841029064609x4,81.812
100TF09110410096104100846411x5,82.28
160TF09116410096110100847011x5,83.28
200TF09120410096114100847411x5,838
250TF091254100108114108847411x5,84.18
315TF091324100120115118907811x5,84.84
400TF091404100120125118908811x5,85.54
500TF091504100120135120909811x5,86.54
600TF0916341001501151221228413x79.12
800TF09180410012013514512210513x78.92
1000TF09210410015014514512211413x711.52
1600TF09216410015016514512213513x714.32
2000TF09220410019514017715011018x1018.21
2500TF09225410019515017715012018x1020.811
3000TF09230410019517617715014418x1024.91

DOWNLOADABLE

Documents

pdf

Descargar ficha técnica

stp-archivo

Descargar Plano

pdf

Descargar catálogo

pdf

Download catalogue

Mercados suministrados

Sectors


Renewable energy


Industry


Other sectors

ISOLATION TRANSFORMERSTSC SERIES

ISOLATION TRANSFORMERSTSC SERIES

Other products

WE MEET YOUR NEEDS

Tailor-made products

If you cannot find what you are looking for, our Technical Department shall look into each project and provide immediate support and personalized service.