SAFETY TRANSFORMERS
Single Phase Safety Transformer
230VAC -
12 / 24VAC
Details
PRIMARY VOLTAGE: 230VAC
SECONDARY VOLTAGE: 12 / 24VAC
STANDARD: In accordance with EN-61558-2-6
ISOLATION CLASS: T40/F
DIELECTRIC STRENGTH:
3600V (between primary and secondary)
3500V (between primary and mass)
3600V (between primary and secondary)
3500V (between primary and mass)
PROTECTION DEGREE: IP00
FREQUENCIES: 50 / 60Hz
CONNECTION: Screw faston terminals
FIXINGS: Using angles DIN 41307
WINDING: Enamelled copper wire class H. Separated primary and secondary (galvanic separation)
Safety transformers are intended to supply electric devices where a circuit separation is required. Protected against humidity by means of resin impregnation
Code:
- Technical specifications
- Download documents
- Industry sectors
SPECIFICATIONS
TECHNICAL FEATURES
| Power (KVA) | Code | Dimension A | Dimension B | Dimension C | Dimension D | Dimension H | Dimension E | Dimension F | Dimension S | Dimension MxN | Weight (Kg) | Packing |
|---|---|---|---|---|---|---|---|---|
| 40 | TS010403200 | 75 | 74 | 42 | 1 | |||
| 63 | TS010633200 | 84 | 94 | 46 | 1.4 | |||
| 100 | TS011103200 | 84 | 102 | 57 | 1.8 | |||
| 160 | TS011163200 | 96 | 104 | 64 | 2.5 | |||
| 200 | TS011203200 | 96 | 108 | 69 | 2.8 | |||
| 250 | TS011253200 | 108 | 110 | 69 | 3.5 | |||
| 315 | TS011323200 | 108 | 121 | 75 | 3.9 | |||
| 400 | TS011403200 | 120 | 115 | 78 | 4.8 | |||
| 500 | TS011503200 | 120 | 132 | 88 | 5.7 | |||
| 360 | TS011633200 | 120 | 141 | 98 | 6.4 | |||
| 800 | TS011803200 | 150 | 125 | 85 | 7.9 | |||
| 1000 | TS012103200 | 150 | 132 | 95 | 9.3 |